circuit breaker 3VA5 UL frame 125 3-pole, starter protection TM120M, AM, In=2A without overload protection short-circuit protection Ii=5...12 x In without connection

Model
product brand name SENTRON
product designation Molded-case circuit breaker
product designation / according to UL file HEAP
design of the product Starter protection
design of the load switch / according to UL 489 / Heating, Air Conditioning, and Refrigeration circuit breaker (HACR Type) Yes
design of the load switch / according to UL 489 / High-Intensity-Discharge circuit breaker (HID Type) No
design of the load switch / according to UL 489 / Switching Duty circuit breaker (SWD Type) No
design of the overcurrent release TM120M
protection function of the overcurrent release I
number of poles 3
General technical data
insulation voltage / rated value 800 V
operating voltage / at AC / rated value 690 V
power loss [W] / maximum 4 W
power loss [W] / for rated value of the current / at AC / in hot operating state / per pole 1.43 W
mechanical service life (operating cycles) / typical 20 000
electrical endurance (operating cycles) / at AC-1 / at 380/415 V 8 000
electrical endurance (operating cycles) / at AC-1 / at 690 V 4 000
electrical endurance (operating cycles) / at 480 V 8 000
electrical endurance (operating cycles) / at 600 V 4 000
product feature / for neutral conductors / upgradable/retrofittable / short-circuit and overload proof No
product function
● communication function No
● phase failure detection No
● other measurement function No
Net Weight 918 g
Current
marking / according to UL 489 / 100%-rated breaker No
operational current
● at 40 °C 2 A
● at 45 °C 2 A
● at 50 °C 2 A
● at 55 °C 2 A
● at 60 °C 2 A
● at 65 °C 2 A
● at 70 °C 2 A
Switching capacity according to IEC 60947
maximum short-circuit current breaking capacity (Icu)
● at 240 V 150 kA
● at 415 V 70 kA
● at 690 V 10 kA
operating short-circuit current breaking capacity (Ics)
● at 240 V 150 kA
● at 415 V 70 kA
● at 690 V 5 kA
short-circuit current making capacity (Icm)
● at 240 V 330 kA
● at 415 V 154 kA
● at 690 V 17 kA
design of short-circuit protection For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter
Adjustable parameters
adjustable response value setting current (Ii) / for I-tripping
● minimum 10 A
● maximum 24 A
adjustable setting current (InN) / for N-tripping
● minimum 0 A
● maximum 0 A
product function / grounding protection No
Mechanical Design
product component
● undervoltage release No
● voltage trigger No
● trip indicator No
height [in] 5.51 in
height 140 mm
width [in] 3 in
width 76.2 mm
depth [in] 3.01 in
depth 76.5 mm
Connections
arrangement of electrical connectors / for main current circuit Without connection
type of electrical connection / for main current circuit Without
Auxiliary circuit
number of CO contacts / for auxiliary contacts 0
Accessories
product extension / optional / motor drive Yes
Environmental conditions
protection class IP / on the front IP40