6ES7148-4PC00-0HA0

New product

Siemens 6ES7148-4PC00-0HA0

SIMATIC ET200pro PS Regulated power supply in protection type IP67 input: 3 AC 400-480 V output: 24 V/8 A DC

Technical Product Detail Page https://i.siemens.com/1P6ES7148-4PC00-0HA0
input
type of the power supply network 3-phase AC
supply voltage at AC
● minimum rated value 400 V
● maximum rated value 480 V
● initial value 340 V
● full-scale value 550 V
supply voltage at AC 320 ... 340 V for max. 1 min
wide range input Yes
overvoltage overload capability Implemented internally with varistors
buffering time for rated value of the output current in the event of power failure minimum 15 ms
operating condition of the mains buffering at Vin = 400 V
line frequency 50/60 Hz
line frequency 45 ... 66 Hz
input current
● at rated input voltage 400 V 0.5 A
current limitation of inrush current at 25 °C maximum 40 A
I2t value maximum 3.5 A²·s
fuse protection type T 4 A
fuse protection type in the feeder Required: Circuit breaker 3RV2011-1DA10 or 3RV2711-1DD10 (UL 489)
output
voltage curve at output Controlled, isolated DC voltage
output voltage at DC rated value 24 V
output voltage
● at output 1 at DC rated value 24 V
output voltage adjustable No; -
relative overall tolerance of the voltage 3 %
relative control precision of the output voltage
● on slow fluctuation of input voltage 0.5 %
● on slow fluctuation of ohm loading 0.5 %
residual ripple
● maximum 200 mV
voltage peak
● maximum 250 mV
display version for normal operation Green LED for 24 V OK
type of signal at output max. 30 V, 10 mA; Power-Good (High-Pegel 1L+ for Vout in range 21.3 ... 29 V); Overtemperature warning at least 30 s before switch-off (high level 1L+ when the max. internal temperature is exceeded)
behavior of the output voltage when switching on Overshoot of Vout < 2 %
response delay maximum 1.5 s
voltage increase time of the output voltage
● typical 40 ms
output current
● rated value 8 A
● rated range 0 ... 8 A
supplied active power typical 192 W
short-term overload current
● on short-circuiting during the start-up typical 50 A
● at short-circuit during operation typical 50 A
duration of overloading capability for excess current
● on short-circuiting during the start-up 100 ms
● at short-circuit during operation 100 ms
bridging of equipment No
efficiency
efficiency in percent 88 %
power loss [W]
● at rated output voltage for rated value of the output current typical 25 W
closed-loop control
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical 0.5 %
relative control precision of the output voltage load step of resistive load 50/100/50 % typical 1 %
setting time
● maximum 2 ms
protection and monitoring
design of the overvoltage protection < 33 V
property of the output short-circuit proof Yes
design of short-circuit protection Electronic shutdown, automatic restart
● typical 9.4 A
enduring short circuit current RMS value
● maximum 10 A
safety
galvanic isolation between input and output Yes
galvanic isolation Protective extra low output voltage Vout according to EN 60950-1 and EN 50178
operating resource protection class Class I
leakage current
● maximum 3.5 mA
● typical 0.4 mA
protection class IP IP67

Siemens satış, Siemens sales, Siemens distribütör, Siemens Türkiye

30 other products in the same category: