Call to us

Close (x)

6ES7231-4HF50-0XB0

New product

Siemens 6ES7231-4HF50-0XB0

SIMATIC S7-1200 G2: SM 1231 analog input, 8 AI; inputs: 8x AI 14 bit ADC (+/-10 V, +/-5 V, +/-2.5 V or 0-20 mA/4-20 mA)

General information
Product type designation SM 1231, AI 8x 14 bit
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
Current consumption, typ. 45 mA
from backplane bus 5 V DC, typ. 75 mA
Power loss
Power loss, typ. 2.5 W
Analog inputs
Number of analog inputs 8; Current or voltage differential inputs
permissible input voltage for voltage input (destruction limit), max. 35 V
permissible input current for current input (destruction limit), max. 40 mA
Cycle time (all channels) max. 1.25 ms; at 400 Hz rejection
Input ranges
● Voltage Yes; ±10V, ±5V, ±2.5V
● Current Yes; 4 to 20 mA, 0 to 20 mA
● Thermocouple No
● Resistance thermometer No
● Resistance No
Input ranges (rated values), voltages
● -10 V to +10 V Yes
— Input resistance (-10 V to +10 V) ≥1 MOhm
● -2.5 V to +2.5 V Yes
— Input resistance (-2.5 V to +2.5 V) ≥1 MOhm
● -5 V to +5 V Yes
— Input resistance (-5 V to +5 V) ≥1 MOhm
Input ranges (rated values), currents
● 0 to 20 mA Yes
— Input resistance (0 to 20 mA) < 290 Ω, > 270 Ω
● 4 mA to 20 mA Yes
— Input resistance (4 mA to 20 mA) < 290 Ω, > 270 Ω
Cable length
● shielded, max. 100 m; shielded, twisted pair
Analog value generation for the inputs
Measurement principle successive approximation
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 13 bit; + sign
● Integration time, parameterizable Yes
● Interference voltage suppression for interference frequency f1 in Hz 40 dB, DC to 60 Hz
Smoothing of measured values
● parameterizable Yes
● Step: None Yes
● Step: low Yes
● Step: Medium Yes
● Step: High Yes
Errors/accuracies
Temperature error (relative to input range), (+/-) 25 °C ±0.1 % / -20 °C to 60 °C ±0.2 % of the full-scale deflection
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.1 %
● Current, relative to input range, (+/-) 0.1 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Common mode voltage, max. 12 V
Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
Diagnoses
● Monitoring the supply voltage Yes
● Wire-break Yes
Diagnostics indication LED
● DIAG LED Yes
● for status of the inputs Yes
Degree and class of protection
IP degree of protection IP20

Siemens satış, Siemens sales, Siemens distribütör, Siemens Türkiye