Call to us

Close (x)

6ES7223-7BF50-0XB0

New product

Siemens 6ES7223-7BF50-0XB0

SIMATIC S7-1200 G2: SB 1223 digital I/O, 4 DI/4 DO 100 kHz; inputs: 4 x DI 24 V DC sink/source, 100 kHz; outputs: 4 x DQ 24 V DC 0.1 A sinking/sourcing transistor, 100 kHz

General information
Product type designation SB 1223, DI 4x 24 V DC/DQ 4x 24 V DC 100 kHz
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V20 or higher
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from backplane bus 5 V DC, typ. 48 mA
Digital inputs
● from load voltage L+ (without load), max. 6 mA; per channel
Digital outputs
● from load voltage L+, max. 15 mA
Power loss
Power loss, typ. 1.7 W
Digital inputs
Number of digital inputs 4; sink / source
● in groups of 4
Input characteristic curve in accordance with IEC 61131, type 1 Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 4
Input voltage
● Rated value (DC) 24 V
● for signal "0" 5 V DC or 0.5 mA
● for signal "1" 15 V DC at 2.5 mA
Input current
● for signal "0", max. (permissible quiescent current) 0.5 mA
● for signal "1", min. 3.3 mA
● for signal "1", typ. 6 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable Yes; 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms
for interrupt inputs
— parameterizable Yes
for technological functions
— parameterizable Yes
Cable length
● shielded, max. 500 m; 500 m shielded, 50 m shielded for HSC inputs
● unshielded, max. 300 m
Digital outputs
Number of digital outputs 4
● in groups of 4
Short-circuit protection Yes
Switching capacity of the outputs
● with resistive load, max. 0.1 A
Output voltage
● Rated value (DC) 24 V
● for signal "0", max. 1 V
● for signal "1", min. L+ (-1.5 V)
Output current
● for signal "1" rated value 0.1 A
Output delay with resistive load
● "0" to "1", max. 1.8 µs
● "1" to "0", max. 1.8 µs
Total current of the outputs (per group)
horizontal installation
— up to 50 °C, max. 0.2 A
Cable length
● shielded, max. 500 m; 500 m shielded, 50 m shielded for PTO outputs
● unshielded, max. 150 m
Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
Diagnoses
● Monitoring the supply voltage Yes
Diagnostics indication LED
● DIAG LED Yes
● for status of the inputs Yes
● for status of the outputs Yes
Potential separation
Potential separation digital inputs
● between the channels No
● between the channels, in groups of 4
● Number of potential groups 1
● between the channels and backplane bus Yes; 707 V DC (type test)
Potential separation digital outputs
● between the channels No
● between the channels, in groups of 4
● Number of potential groups 1
● between the channels and backplane bus Yes; 707 V DC (type test)
Degree and class of protection
IP degree of protection IP20

Siemens satış, Siemens sales, Siemens distribütör, Siemens Türkiye