Siemens 6ES7157-1MA00-0AB0
SIMATIC ET 200AL, MultiFieldbus interface module IM 157-1 MF, PN IO, EtherNet/IP, Modbus TCP, PN security class 1, degree of protection IP67
| General information | ||
| Product type designation | IM 157-1 MF | |
| HW functional status | FS01 | |
| Firmware version | V1.0.x | |
| ● FW update possible | Yes | |
| Vendor identification (VendorID) | 002AH | |
| Device identifier (DeviceID) | 0314H | |
| Manufacturer ID according to ODVA (VendorID) | 0x04E3 | |
| Device ID according to ODVA (Product code) | 0x0FB6 | |
| Product function | ||
| ● I&M data | Yes; I&M0 to I&M4 | |
| ● Isochronous mode | No | |
| ● IRT | Yes | |
| Engineering with | ||
| ● STEP 7 TIA Portal configurable/integrated from version | STEP 7 V19 or higher | |
| ● STEP 7 configurable/integrated from version | from V5.6 | |
| ● PROFINET from GSD version/GSD revision | GSDML V2.4.x | |
| ● Multi Fieldbus Configuration Tool (MFCT) | from V1.5 | |
| Configuration control | ||
| via dataset | Yes | |
| Supply voltage | ||
| power supply according to NEC Class 2 required | No | |
| Load voltage 1L+ | ||
| ● Rated value (DC) | 24 V | |
| ● permissible range, lower limit (DC) | 20.4 V | |
| ● permissible range, upper limit (DC) | 28.8 V | |
| ● Reverse polarity protection | Yes; against destruction | |
| Input current | ||
| Current consumption (rated value) | 80 mA | |
| from load voltage 1L+ (unswitched voltage) | 4 A; Maximum value | |
| from load voltage 2L+, max. | 4 A; Maximum value | |
| Power loss | ||
| Power loss, typ. | 2.5 W | |