SIPLUS S7-1500 CM 1542-5 based on 6GK7542-5DX10-0XE0 with conformal coating, -40…+70 °C, start up -25 °C, communications module for connection of S7-1500 to PROFIBUS DP as DP master and DP Device: S7 and PG/OP communication, time-of-day synchronization, diagnostics
| product type designation | CM 1542-5 | |
| Technical Product Detail Page | https://i.siemens.com/1P6AG1542-5DX10-7XE0 | |
| transfer rate | ||
| transfer rate | ||
| ● at the 1st interface / according to PROFIBUS | 9.6 kbit/s ... 12 Mbit/s | |
| interfaces | ||
| number of interfaces / according to Industrial Ethernet | 0 | |
| number of electrical connections | ||
| ● at the 1st interface / according to PROFIBUS | 1 | |
| type of electrical connection | ||
| ● at the 1st interface / according to PROFIBUS | 9-pin Sub-D socket (RS485) | |
| supply voltage, current consumption, power loss | ||
| type of voltage / of the supply voltage | DC | |
| supply voltage / 1 / from backplane bus | 15 V | |
| relative symmetrical tolerance / at DC | ||
| ● at 15 V | 3 % | |
| consumed current | ||
| ● from backplane bus / at DC / at 15 V / typical | 0.2 A | |
| power loss [W] | 3 W | |
| ambient conditions | ||
| ambient temperature | ||
| ● for vertical installation / during operation | -40 ... +40 °C | |
| ● for horizontally arranged busbars / during operation | -40 ... +70 °C | |
| ● during storage | -40 ... +70 °C | |
| ● during transport | -40 ... +70 °C | |
| ● note | Startup @ -25 °C | |
| installation altitude / at height above sea level / maximum | 5000 m | |
| ambient condition / relating to ambient temperature - air pressure - installation altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) | |
| relative humidity | ||
| ● with condensation / according to IEC 60068-2-38 / maximum | 100 %; RH including condensation/frost (no commissioning when condensation is present), horizontal installation | |
| chemical resistance / to commercially available cooling lubricants | Yes; incl. airborne diesel and oil droplets | |
| resistance to biologically active substances | ||
| ● conformity according to EN 60721-3-3 | Yes; Class 3B2 mold and fungal spores (excluding fauna), Class 3B3 on request | |
| ● conformity according to EN 60721-3-6 | Yes; Class 6B2 mold, fungal and dry rot spores (excluding fauna) | |
| resistance to chemically active substances | ||
| ● conformity according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray in accordance with EN 60068-2-52 (Severity 3). The supplied plug covers must remain in place on the unused interfaces during operation. | |
| ● conformity according to EN 60721-3-6 | Yes | |
| resistance to mechanically active substances | ||
| ● conformity according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation. | |
| ● conformity according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation. | |
| coating / for equipped printed circuit board / according to EN 61086 | Yes; Class 2 for high availability | |
| type of coating / protection against pollution according to EN 60664-3 | Yes; Protection of the type 1 | |
| type of test / of the coating / according to MIL-I-46058C | Yes; Coating discoloration during service life possible | |
| product conformity / of the coating / Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A | Yes; Conformal coating, class A | |
| protection class IP | IP20 | |