Call to us

Close (x)

6ES7158-3AD10-0XA0

New product

Siemens 6ES7158-3AD10-0XA0

General information
Product type designation PN/PN coupler
Firmware version V6.0
● FW update possible Yes
Vendor identification (VendorID) 002AH
Device identifier (DeviceID) 0604H
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode Yes; 500 µs
● Tool changer Yes; Docking station and docking unit
● Local coupling, IO data Yes
— Number of coupling modules 16; in non-isochronous mode, otherwise 3
— Number of coupling submodules per module 4; 1x write, 3x read in non-isochronous mode, otherwise see description in the manual
● Local coupling, data records Yes; in non-isochronous mode
— Number of coupling modules 16
— Number of coupling submodules per module 4; 1x write, 3x read
— Record length, max. 4 096 byte
— FIFO depth in storage mode 8
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V20 or higher
● STEP 7 configurable/integrated from version V5.7 SP3
● PROFINET from GSD version/GSD revision GSDML V2.4.x
Installation type/mounting
Mounting Mounting rail 7.5 mm and 15 mm
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Mains buffering
● Mains/voltage failure stored energy time 10 ms
Input current
Current consumption, max. 360 mA; For 19.2 V input voltage at the right-hand supply terminal, including 2 plugged BA 2x LC
Inrush current, max. 1.6 A
I²t 0.031 A²·s
from supply voltage 1L+, max. 320 mA; For 19.2 V input voltage at the left-hand supply terminal, including 2 plugged BA 2x LC
Power loss
Power loss, typ. 4 W; For 24 V input voltage and 2 plugged BA 2x RJ45 If BusAdapters with an optical interface are plugged, there is an additional 750 mW per optical interface (3 W with 2 plugged BA 2x LC)
Address area
Address space per module
● Address space per module, max. 254 byte; max. 254 bytes of input data and 253 bytes of output data
Address space per station
● Address space per station, max. 1 440 byte; per input / output
Hardware configuration
Submodules
● Number of submodules per station, max. 116
Interfaces
Number of PROFINET interfaces 2; One PROFINET interface per line side
Optical interface Yes; Via SIMATIC BusAdapter
Transmission rate, max. 100 Mbit/s